Description
Specifications
Notifier® by Honeywell | Photoelectric Smoke Detection | |||||||
Product Type | FSP-851 | |||||||
Operating Temperature range | 0°C to 49°C (32°F to 120°F). | |||||||
Rotary address switches for point identification and quick installation | ||||||||
Dual LEDs for 360° visibility | ||||||||
Sensitivity | 0.5% to 2.35% per foot obscuration | |||||||
Relays | 3 Form-C; programmable | |||||||
Size | 2.1″ (5.3 cm) high; base determines diameter | |||||||
– B210LP(A): 6.1″ (15.5 cm) diameter | ||||||||
– B501(A): 4.1″ (10.4 cm) diameter | ||||||||
– B200S(A): 6.875″ (17.46 cm) diameter | ||||||||
– B200SR(A): 6.875″ (17.46 cm) diameter | ||||||||
– B224RB(A): 6.2″ (15.748 cm) diameter | ||||||||
– B224BI(A): 6.2″ (15.748 cm) diameter | ||||||||
UL/ULC Listed Velocity Range | 0-4000 ft/min. (1219.2 m/min.), suitable for installation in ducts | |||||||
Relative Humidity | 10%-93% noncondensing | |||||||
Thermal Ratings | Fixed-temperature setpoint 135°F (57°C) | |||||||
Electrical Specifications | ||||||||
Voltage Range | 15-32 volts DC peak | |||||||
Standby Current (max. avg.) | 300μA @ 24VDC (one communication every five seconds with LED enabled). | |||||||
LED Current (max.) | 6.5mA @ 24 VDC (“ON”). | |||||||
Specifications subject to change without notice.
Features :
• Sleek, low-profile design
• Addressable-analog communication
• Stable communication technique with noise immunity
• Low standby current
• Two-wire SLC connection
• Compatible with FlashScan® and CLIP protocol systems
• Rotary, decimal addressing (1-99 on CLIP systems, 1-159 on FlashScan systems)
• Optional remote, single-gang LED accessory
• Dual LED design provides 360° viewing angle
• Visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm (FlashScan systems only)
• Remote test feature from the panel
• Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1(FlashScan systems only)
• Built-in functional test switch activated by external magnet
• Built-in tamper-resistant feature
• Sealed against back pressure
• Constructed of off-white fire-resistant plastic, designed to commercial standards, and offers an attractive appearance.
• 94-5V plastic flammability rating
• SEMS screws for wiring of the separate base
• Optional relay, isolator, and sounder bases
Agency Listings and Approvals :
• UL Listed: S1115
• ULC Listed: S1115 (FSP-851A, FSP-851RA, FSP-851TA)
• MEA Listed: 225-02-E
• FM Approved
• CSFM: 7272-0028:0206
• Maryland State Fire Marshal: Permit # 2122
• BSMI: CI313066760036
• CCCF: Certif. # 2004081801000017 (FSP-851T)
Certif. # 2004081801000016 (FSP-851)
• U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0 (NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)
• Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS-320C, excluding B210LP(A))