Description
- Features
- Technical Data
- Accessories
- Additional information
- Downloads
Completely bus supplied alarm device
Powered loop compatible
Low power consumption
Up to 32 alarm devices for each powered loop
Each alarm device has built-in isolator
Tones can be used for other purposes in addition to warning of fire, making the device ideal for use in schools etc.
Soft start option, ideal for hospitals and nursing homes
Acoustic pressure up to 99 dB(A) @ 1 m
Volume programmable in 8 steps via tools 8000
Up to 26 different languages are available
20 different signaling tones, including DIN tone
Multilingual speech alarm in 5 different languages
Alarm signaling, evacuation, and test alarm can each be programmed in different languages
Speech alarm, 5 pre-programmed alarm texts and other country-typical alarm signals
Flash intensity equivalent to 3W Xenon flash light
| ESSER By Honeywell | |
| Operating voltage | 8 … 42 V DC (via powered loop) |
| Quiescent current @ 19 V DC |
approx. 55 μA
|
| Quiescent current @ FACP battery |
approx. 300 μA @ 42 V
|
| Sound level |
97 dB (A) +/- 2 dB @ 1 m
|
| Luminous intensity |
max. 24.4 cd peak/ 4.1 cd effective (red flash)
|
| Frequency of flash |
approx. 3 Hz
|
| Lighting energy |
approx. 3 Y
|
| Ambient temperature |
-10 °C … 50 °C
|
| Storage temperature |
-10 °C … 55 °C
|
| Type of protection |
IP 30
(IP 65 with socket 806201 / 806202)
|
| Housing |
ABS plastic
|
| Air humidity |
< 95 % (non condensing)
|
| Color |
red, similar to RAL 3020
|
| Weight |
approx. 300 g
|
| Specification |
EN 54-3 acoustic signaling device
|
| Dimensions | Ø: 112 mm D: 75 mm Ø: 112 mm D: 90 mm (with IP 65 base) |
806202 IP 65 base, red
Please consider:
– Admissible maximum loop length
– Admissible maximum number of single alarm device types
– Maximum number of 127 bus devices for each loop
FACP IQ8Control from version V3.04
FACP FlexES Control
esserbus-Plus functionality
Programming software tools 8000 from version V1.09
Attention – an operation with the FACP’S 8000 C/M is not possible!!!
For upgrading 8000 C/M control units, IQ8Lumivox signaling devices must be used. If required, please contact our returns department.
For checking the battery capacity of FACP, the value “quiescent current @ FACP battery“ can be added.