Description
- Features
- Technical Data
- Additional information
- Downloads
Provides a voltage-free contact controlled by the remote output of a detector
Draws negligible current
A lot of space for wire connection
Automatic closing of the loop bus wiring system for detector extraction
Detector extraction locking is enclosed in the base
| ESSER By Honeywell | |
| Current consumption | 5 µA (w/o detector, active relay) |
| Contact load relay |
30 V DC/1 A
|
| Application temperature |
-20 °C … 72 °C
|
| Storage temperature |
-25 °C … 75 °C
|
| Connection terminal |
Ø 0.6 mm to 2 mm²
|
| Material |
ABS
|
| Air humidity |
< 95 % (non-condensing)
|
| Color Weight |
white, similar to RAL 9010
approx. 80 g
|
| Dimensions | Ø: 117 mm H: 24 mm (incl. detector 62 mm) |
Cable entry on the side or through the bottom plate. Connection of remote indicators not allowed!
Wago clamps for looping in wires, e.g. type 243-204 (Ø 0.5 mm – 1.0 mm) or 273-104 (0.75 mm²- 2.5 mm²) can be mounted on the detector base.
Not suitable for application with IQ8Quad with integrated alarm device Part No. 802383, 802384, 802385 and 802386 as well as 802385.SVxx and 802386.SVxx!