Description
- Technical Data
- Accessories
- Additional information
- Downloads
| ESSER By Honeywell | |
| Operating voltage Quiescent current @ 19 V DC |
8 … 42 V DC approx. 50 μA |
| Alarm current @ 9 V DC Area to be monitored |
typ. 18 mA
max. 110 m²
|
| Height to be monitored |
max. 12 m
|
| Ambient temperature (Ta) Application temperature |
-20 °C … 70 °C
-20 °C … 70 °C
|
| Storage temperature Max. Output current (Io) |
-25 °C … 75 °C
10 mA
|
| Max. Input Voltage (Ui) Max. Input current (Ii) Max. internal capacity (Ci) |
21 V DC
252 mA
1 nF
|
| Explosion protection |
Ex ib IIC T4 Gb
|
| Type of protection |
IP 43 (incl. base + option)
|
| Material |
ABS
|
| Air humidity |
< 95 % (non condensing)
|
| Color |
white, similar to RAL 9010
|
| Weight |
approx. 110 g
|
| Detector specification |
EN 54-7:2006
|
| EC-type examination certificate |
TÜV 09 ATEX 554910
|
| Dimensions | Ø: 117 mm H: 49 mm (62 mm incl. base) |
805590 Standard detector base for IQ8Quad
Detector bases are not supplied as standard.
Intrinsically safe fire detection equipment is defined as “equipment and wiring which is incapable of releasing sufficient electrical or thermal energy under normal or abnormal conditions to cause ignition of a specific hazardous atmosphere mixture in its most easily ignited concentration”. This basically means that intrinsically safe equipment and wiring operates using electrical and thermal energy below the level that would be required to spark an explosion in a hazardous area such as an oil refinery, Oil Rigs/Platforms, FPSO’s.
Fully addressable devices for installation in hazardous areas with direct connection of the Ex barrier (Part No. 804744) on the loop, without spending a loop address for the connection via a transponder as in case of the conventional connection.
Additional detectors for the explosion zones can be found in the chapters manual call points and special detectors. Detailed information about installation and operation can be found in the documentation (Part No. 798920) on our website.
All of the following IQ8Quad intrinsically safe fire detectors must be operated with the Part No. 805590 base. In the case of operation in standard zones, no individual addressing is possible!
For usage in zone 1 and zone 2 in case of operation
– with individual addressing the Ex barrier Part No. 804744,
– in conventional zones the Ex barrier Part No. 764744 must be used!
The Ex barrier separates intrinsically safe and non-intrinsically safe circuits before the explosion prone area to be monitored (explosion zone).