Description
- Technical Data
- Accessories
- Additional information
- Downloads
| ESSER By Honeywell | |
| Operating voltage Quiescent current @ 19 V DC |
8 … 42 V DC approx. 40 μA |
| Alarm current @ 9 V DC Area to be monitored |
typ. 18 mA
max. 30 m²
|
| Height to be monitored |
max. 7.5 m
|
| Ambient temperature (Ta) Application temperature |
-20 °C … 70 °C
-20 °C … 50 °C
|
| Storage temperature Max. Output current (Io) |
-25 °C … 75 °C
10 mA
|
| Max. Input Voltage (Ui) Max. Input current (Ii) Max. internal capacity (Ci) |
21 V DC
252 mA
1 nF
|
| Explosion protection |
Ex ib IIC T4 Gb
|
| Type of protection |
IP 43 (incl. base + option)
|
| Material |
ABS
|
| Air humidity |
< 95 % (non condensing)
|
| Color |
white, similar to RAL 9010
|
| Weight |
approx. 110 g
|
| Detector specification |
EN 54-5 A1R:2002
|
| EC-type examination certificate |
TÜV 09 ATEX 554910
|
| Dimensions | Ø: 117 mm H: 49 mm (62 mm incl. base) |
805590 Standard detector base for IQ8Quad
Special marking for heat detector on light pipe: black ring