Slimline design
Low power consumption
Plug-in connection terminals (two direction)
Optional terminal terminals
Triple key function (test, open, reset)
Detectors that are not ready for operation can be marked with the “Out of order” label by reversing the enclosed glass pane
| ESSER By Honeywell | |
| Operating voltage | 8 … 42 V DC |
| Quiescent current @ 19 V DC |
approx. 45 μA
|
| Alarm current w/o communication curtain |
approx. 18 mA
|
| Alarm display |
red LED 1 / yellow tab
|
| Operation indicator |
LED, green
|
| No. of detector/zone |
max. 127 MCP per loop
|
| Application temperature |
-20 °C … 70 °C
|
| Storage temperature |
-30 °C … 75 °C
|
| Connection terminal |
max. 2.5 mm² (AWG 26-14)
|
| Type of protection |
IP 43 (in housing)
|
| Housing |
ASA plastic
|
| Color |
red, similar to RAL 3020
|
| Weight |
approx. 110 g
|
| Detector specification |
EN 54-11, type A
|
| Dimensions |
W: 88 mm H: 88 mm D: 21 mm
W: 88 mm H: 88 mm D: 57 mm (with surface mount housing)
|
704980 Surface mount housing
If the glass pane is replaced with the optionally available plastic pane with reset function, the MCP can be reset from the outside using the key.
For the surface mounting of the MCP the surface mount base Part No. 704980 must be ordered separately, if the cable wasn’t laid about a standard flush mount wall socket.
Type a definition – single action in accordance with EN 54-11 § 3.4.1
(excerpt taken from EN standard):
Manual fire alarm unit, for which the alarm status is automatically set (additional alarm triggering is not required) after the fragile element has been broken or its position has been changed.
1x Plastic operating panel 704964
1x Key 704966
1x Multilingual paper insert with “Out of order” pictogram included