Description
| Hochiki® FireNET® | ASBL – Low Frequency Sounder Base | |||||||
| Operating Voltage | 17 – 41 VDC | |||||||
| SLC Current Consumption | 154μA (Standby and Alarm) | |||||||
| Auxiliary Power | 16—31 VDC | |||||||
| Auxiliary Current Consumption | 2.8mA (Standby) | |||||||
| Auxiliary Current Consumption | 72mA @ 33VDC (Alarm) | |||||||
| 95mA @ 24VDC | ||||||||
| 140mA @ 16VDC | ||||||||
| Sound Pressure Level | 85dB | |||||||
| Max. Quantity per Loop | 127 | |||||||
| UL Ambient Installation Temperature Range | 32°F (0°C) – 100°F (38°C) | |||||||
| Operating Temperature Range | 32°F (0°C) – 122°F (50°C) | |||||||
| Relative Humidity | 93% RH Non-Condensing | |||||||
| Base Diameter | 6.6” | |||||||
| Base Height | 3.1” | |||||||
| Compatible Sensors | ALG-V, ALK-V, ALN-V, AIE-EA, ATG-EA, ATJ-EA, ACA-V, ACC-V, ACD-V | |||||||
Specifications subject to change without notice.
• UL268 and UL464 listed
• Programmable evacuation codes – Continuous, March, ANSI Temporal patterns
• 520Hz low frequency alarm signal meets NFPA requirements for sleeping areas
• Base learns the sensor address and assumes an upper range address (128-254)
• Up to 127 sensors and 127 ASBLs can be used on one SLC loop
• Programmable activation by general alarm, by zone and/or by individual address
• High sound pressure level (85dB SPL at 10 feet)
• Signaling Listed
• FM APPROVED – Pending
• CSFM Listed – 7300-0410:0210
• ISO 9001-2008