Description
Hochiki® FireNET® | FRCMA – Fast Response Contact Monitoring Module | |||||||
Supply Voltage (S-SC) | 25.3 ~ 39 VDC | |||||||
Average Current | 630μA (Typical) | |||||||
Consumption | 6.3mA (Alarm) | |||||||
SCI On Resistance | 40m ohm Max. (Normal Condition) | |||||||
SCI Fault Detection Threshold | 12 volts (Typical) | |||||||
SCI Isolation Current (Short Circuit Condition) | 10mA (Typical) | |||||||
Maximum Quantity Per Loop | 127 | |||||||
Dimensions | 4.2″W x 4.7″H x 1.4″D | |||||||
Ambient Temperature | 32°F (0°C) ~ 120°F (49°C) | |||||||
Mounting | 4″ square electrical box | |||||||
Relative Humidity | 90% RH Non-condensing |
Specifications subject to change without notice.
• Single input contact monitor
• Fast, reliable contact monitoring utilizing the Hochiki DCP (Digital Communications Protocol)
• Two different mounting configurations
• 127 devices can be used per DCP loop
• Bi-colored indicating LED provides module status (Both Models)
• Yellow LED indicates a short circuit condition (FRCMA-I only)
• Can be programmed to monitor Normally Open (NO) or Normally Closed (NC) contacts in Class B
• Operates on Class A or Class B SLC loop
• Accepts up to 14 AWG wire
• UL 864 Listed
• Signaling Listed – S5694
• FM APPROVED – 3036830
• CSFM Listed – 7300-0410:150
• ISO 9001-2008