Description
Specifications
| Notifier® by Honeywell | Photoelectric Smoke Detector | |||||||
| Product Type | FSL-751 | |||||||
| Operating temperature | 0° to 38°C (32° to 100°F) | |||||||
| Rotary address switches for point identification and quick installation | ||||||||
| Dual LEDs for 360° visibility | ||||||||
| Relative Humidity | 10% – 93% noncondensing | |||||||
| Size | 2.0″ (51 mm) high; base determines diameter | |||||||
| – B210LP(A): 6.1″ (15.5 cm) diameter | ||||||||
| – B501(A): 4.1″ (10.4 cm) diameter | ||||||||
| – B200S(A): 6.875″ (17.46 cm) diameter. | ||||||||
| – B200SR(A): 6.875″ (17.46 cm) diameter. | ||||||||
| – B224RB(A): 6.2″ (15.748 cm) diameter. | ||||||||
| Electrical Specifications | ||||||||
| Operating voltage range | 15 to 32 VDC peak | |||||||
| Maximum average standby current | 230 A @ 24 VDC (no communication). 330 A @ 24 VDC | |||||||
| (one communication every 5 seconds with LED blink enabled). | ||||||||
| Maximum alarm current | 6.5 mA @ 24 VDC (LED “ON”). | |||||||
Specifications subject to change without notice.
Features :
• Very Intelligent Early Warning (VIEW®) smoke detection
• Advanced laser light source and patented optical design
• Sleek low-profile housing (1.66″/42.164 mm height)
• Sensitivity :
– 0.03% to 1.00% for CLIP systems
– 0.02% to 2.00% for all other panels
• Rotary, decimal addressing (1-99 on CLIP systems, 1-159 on FlashScan systems)
• Dual bi-color (red/green) LEDs flash green when Normal and are steady red in Alarm
• Compatible with the AFP-300, AFP-400, NFS-640, NFS2-640, NFS-320, NFS-3030, and NFS2-3030 (all software releases)
• Dual LED design provides 360° viewing angle
• Built-in magnetic test switch, or automatic test commanded from panel
• Optional remote, single-gang LED accessory, RA100Z(A)
• Optional relay, isolator, or sounder bases
Agency Listings and Approvals :
• UL Listed: S1115
• ULC Listed: S1115
• MEA Listed: 128-07-E (NFS2-640, NFS-320); 3-02-E
• FM Approved
• CSFM: 7272-0028:0218
• BSMI: CI313066760036
• CCCF: Certif. # 2004081801000015
When used with NFS2-640/NFS-320, MARINE-EQ, and appropriate seismic bracket, these detectors are approved by the following agencies :
– U.S. Coast Guard: 161.002/50/0 (Standard 46 CFR).
– Lloyd’s Register: 11/600013 (ENV 3 category).