Description
FireNET® Series 4127 | Analog Addressable Fire Alarm Control Panel | |||||||
Primary AC | 120VAC @ 2.1 Amps 60hz or 220VAC @ 1.1Amps 50hz | |||||||
Output DC | 24VDC @ 5.25 Amps (4 Amps available for system power) | |||||||
Power Supply |
5.25 Amps integrated
|
|||||||
Charger Current |
1.5 Amps max.
|
|||||||
Dimensions |
14.5″ W x 24″ H x 5″ D
|
|||||||
Weight |
31 lbs. (without batteries)
|
|||||||
Color |
Red (optional gray)
|
|||||||
Material |
ABS/steel enclosure
|
|||||||
Display |
8 line x 40 character LCD (320 characters total)
|
|||||||
Network |
Dual RS485 ports (64 panels max.)
|
|||||||
Zones |
500 network wide software zones per system
|
|||||||
SLC loops |
2 or 4 (class A, “style 6 or 7” or class B, “style 4”)
|
|||||||
Devices per loop |
127 sensors & modules, plus 127 analog sounder bases, 254 total
|
|||||||
Addresses per panel |
(800 addresses+sub-addresses max. per panel)
|
|||||||
NAC Outputs |
(4) 2.5 Amps @ 24VDC (class B)
|
|||||||
Relay Outputs |
(5) Form C 1 Amp @ 30VDC
|
|||||||
Voltage Outputs |
(3) 500mA @ 24VDC
|
|||||||
Aux. Power |
500mA @ 24VDC
|
|||||||
Aux. Inputs |
(8) digital pull downs
|
|||||||
PC Port / Printer | RS232 |
Model | Description | |||||
FN-2127-DDW | FACP (2 Loop/5.25 Amps) | |||||
FN-2127-DDWN | FACP (2 Loop/5.25 Amps) (w/Network) | |||||
FN-4127-DDW |
FACP (4 Loop/5.25 Amps)
|
|||||
FN-4127-DDWN |
FACP (4 Loop/5.25 Amps) (w/Network)
|
• UL 864 9th Edition Listed
• Seismic certified
• Analog design using Hochiki’s advanced DCP protocol for fast and robust communication
• Up to 127 sensors & modules, plus 127 analog sounder bases, for a total of 254 points possible per loop
• Uses standard wire, no shielded or twisted pair required on SLC loops
• Supports Class B (style 4) and Class A (style 6 or 7) SLC loops
• 4 on board Class B (style Y) NAC circuits rated at 2.5 Amps each
• Programmable sensitivity levels per device & automatic day/night sensitivity modes
• Automatic daily calibration & drift compensation routine
• Large 8-line x 40-character LCD display (320 char.)
• 2 loop (FN-2127 Series) or 4 loop (FN-4127 Series) versions (800 addresses/sub-addr. max.)
• UL 864, Listed – S8255
• Signaling Listed – S6468
– Local Signaling Unit.
– Types: Automatic, manual, waterflow, sprinkler supervisory, Remote Station and Central Station Service (DACT) Non-coded signaling.
• FM Approved – 3033817
• CSFM Listed – 7165-0410:159
• NFPA 70, 72 & 13 Compliant