Description
The detector, HS-WK100L incorportes a self-resetting bimetallic disk element with response indicator. It activates whenever the ambient air temperature reaches the top temperature detector setting.
SPECIFICATION :
Main Model | HK-WK100L |
Type | 2 wire |
Voltage Range |
12~30V DC
|
Alarm Current |
24V DC 30mA
|
Polarization |
Non-polarized
|
Fixed Temperature |
60°C, 70°C, 80°C.
|
Sensitivity | When exposed within an air stream 1 m/sec., 125% higher than its operating temperature, and at 20 C of ambient temperature, the detector will sound an alarm within 90 seconds. |
Alarm Temperature | Comply to EN54, CNS |
Ambient Temperature | -10°C~+55°C |
Ambient Humidity |
0~95%
|
Material |
Fire-Proof plastics
|
Dimensions |
101 (Dia.) x 47 (H)mm
|
Weight |
100gms.
|
Color | White |